Estimation of the inductive current transformer derating for operation with distorted currents

Miniatura

Data

2014

Tytuł czasopisma

ISSN czasopisma

Tytuł tomu

Wydawca

Abstrakt

The aim of the paper is to present a new method for estimation of the CT (Current Transformer) rated primary current and / or load of the secondary winding derating levels for transformation of distorted current in relation to the rated values fixed for transformation of sinusoidal current. This ensures the values of the CT composite errors/transformer correction factors as resulting from its IEC 60044-1/IEEE C57.13 accuracy class in condition of distorted currents transformation.

Opis

Słowa kluczowe

current transformer, distorted current, derating conditions, composite error, transformer correction factor, accuracy class

Cytowanie

Bulletin of the Polish Academy of Sciences Technical Sciences, Vol. 62, Issue 2, 2014, Pages 363–366

item.page.endorsement

item.page.review

item.page.supplemented

item.page.referenced